Factory power: amp to kVA converter
On Malaysia's 400 V three-phase supply, multiply the amps by about 0.69 to get kVA: 100 A is about 69 kVA, 300 A about 208 kVA and 1,000 A about 693 kVA. For kW, multiply kVA by the power factor, about 0.85 for a typical factory.
Rates checked 27 November 2026. These are estimates; your lawyer, tax agent or bank confirms the final figures.
Formula
Three-phase: kVA = 1.732 × volts × amps ÷ 1,000. Single phase: kVA = volts × amps ÷ 1,000. kW = kVA × power factor.
Quick table (400 V three-phase)
| Amps | kVA |
|---|---|
| 60 A | 42 |
| 100 A | 69 |
| 150 A | 104 |
| 200 A | 139 |
| 300 A | 208 |
| 500 A | 346 |
| 800 A | 554 |
| 1,000 A | 693 |
How much power do you need?
- List every machine with its rated kW (on the nameplate or in the manual), plus air-conditioning, compressors and lighting.
- Add them up and divide by 0.85 to get kVA.
- Add 20% to 25% for start-up loads and growth.
- Convert to amps: amps = kVA × 1,000 ÷ (1.732 × 400).
If the factory's existing supply is lower, ask TNB through an electrical contractor whether it can be upgraded and how long it takes. Large loads may need a substation on site. We check the supply in amps for every factory we market.