Factory power: amp to kVA converter

On Malaysia's 400 V three-phase supply, multiply the amps by about 0.69 to get kVA: 100 A is about 69 kVA, 300 A about 208 kVA and 1,000 A about 693 kVA. For kW, multiply kVA by the power factor, about 0.85 for a typical factory.

Apparent power (kVA)–Real power at 0.85 power factor (kW)–

Rates checked 27 November 2026. These are estimates; your lawyer, tax agent or bank confirms the final figures.

Formula

Three-phase: kVA = 1.732 × volts × amps ÷ 1,000. Single phase: kVA = volts × amps ÷ 1,000. kW = kVA × power factor.

Quick table (400 V three-phase)

AmpskVA
60 A42
100 A69
150 A104
200 A139
300 A208
500 A346
800 A554
1,000 A693

How much power do you need?

  1. List every machine with its rated kW (on the nameplate or in the manual), plus air-conditioning, compressors and lighting.
  2. Add them up and divide by 0.85 to get kVA.
  3. Add 20% to 25% for start-up loads and growth.
  4. Convert to amps: amps = kVA × 1,000 ÷ (1.732 × 400).

If the factory's existing supply is lower, ask TNB through an electrical contractor whether it can be upgraded and how long it takes. Large loads may need a substation on site. We check the supply in amps for every factory we market.